How to Adjust Parameters of a Thermal Flow Switch?
Parameter Adjustment Procedure?
Based on technical documentation for the NK300 Series and NK Series thermal flow switches, follow these steps:
I. Pre-Adjustment Preparation?
Verify Model Functions?
NK300 Series?: Adjust via potentiometer; LED indicators display flow status.
NK Series? (with integrated temperature): Adjust via buttons; 0.96-inch color screen displays flow/temperature.
Installation Requirements?
Ensure the probe is fully immersed in the medium, avoiding bubbles or impurities.
Confirm power supply (24V DC) and output signal wiring (PNP/NPN/relay, etc.).
II. Parameter Adjustment Steps?
1. NK300 Series (Potentiometer Adjustment)?
Flow Setting?
Rotate the potentiometer knob (no need to remove sealed screws). Observe 6 LED indicators:
Number of lit LEDs indicates flow velocity (all lit = flow達標).
Adjust threshold per medium type:
Water: 1–150 cm/s; Oil: 3–300 cm/s; Air: 20–2000 cm/s.
Response Time?
Default: 2 seconds (typical). Adjust sensitivity by extending/shortening initialization (~8s).
2. NK Series (Button + Color Screen Adjustment)?
Flow/Temperature Setting?
Enter setup mode via device buttons; screen displays real-time flow/temperature.
Configure per technical specs:
Flow dead zone: ≤0.01 m/s; Temperature gradient: ≤4°C/s.
Support for IO-Link or analog output calibration (e.g., 4–20mA ? flow range).
III. Key Considerations?
Medium Compatibility?
Scaling/oil contamination may reduce sensitivity. Clean regularly (anti-scaling coating delays fouling).
Electrical Safety?
Ensure stable power during adjustment to avoid reverse polarity/short-circuit triggers.
Function Verification?
Simulate flow changes (e.g., pump start/stop) to confirm signal output (relay actuation or PNP/NPN switching).
IV. Technical Parameters Reference?
Pressure Resistance?: 100 Bar
IP Rating?: IP67
Repeatability?: ±2% (NK300 Series)
Temperature Compensation?: Auto-calibration for NK Series (±1.5°C accuracy).