?? I. Typical Application Scenarios & Threshold References
Fire Protection Systems?
Standard Type?: Activation range ?0.035–0.05MPa? (pump start pressure)
Preaction Systems?: Lower sensitivity range ?0.03–0.05MPa?
Rail Transportation?
Train braking system trigger point: ?3.8 Bar? (≈ ?0.38MPa?), cuts off traction enable when line pressure drops below this value.
Industrial Equipment?
Reference Point?: Typically ?0.5MPa? (calibrated at standard atmospheric pressure)
Action Threshold?: Common setting ?0.8MPa? (adjusted via precision wrench)
Hysteresis Range?: Maintain ?0.05–0.2MPa? (too small causes frequent cycling; too large reduces accuracy)
?? II. Adjustment Procedures
Mechanical Pressure Switches?
Increasing Threshold?:
- Loosen adjustment screw counterclockwise
- Pressurize to target value
- Tighten clockwise until contacts activate (audible "click")
Differential Setting?:
Lower limit = Upper limit (e.g., 0.8MPa) - Desired differential (e.g., 0.3MPa → 0.5MPa)
Electronic Pressure Switches?
Modify setpoint via menu interface (long-press function key for calibration mode on some models)
PID algorithm optimization for dynamic conditions
?? III. Key Parameter Standards
Parameter? ?Recommended Range? ?Application Example?
Safety Margin? ≥1.2× operating pressure Rated 10MPa switch ≤8MPa test
Hysteresis Rate? 5%–15% of full scale Food machinery: 5–8%, Industrial: 10–15%
Action Error? ≤±1.0% FS 10MPa scale error ≤0.1MPa
? IV. Critical Prohibitions
Never exceed rated range?: Test pressure ≤80% of rated value
Avoid insufficient hysteresis?: Causes equipment cycling → reduced lifespan
Power off before adjustment?: Always disconnect system power
Post-adjustment Validation?: Cycle pressure 3×; actuation deviation ≤50% of accuracy class